Miten voimme auttaa sinua?

Product 

For all information regarding leak tightness tests, please consult our technical manual. Page 105-107 chapter 7.21 Leak tightness and pressure resistance tests.

Vond je dit antwoord nuttig?

Use appropriate formers and bend springs. References BI, BA, BM and BM-F

Vond je dit antwoord nuttig?

Both grades comply with operational conditions 10 bar at 70 °C however the standard pipe has a thicker aluminium core and even higher performance in fail safe conditions.

Vond je dit antwoord nuttig?

A PE-RT or PE-Xc pipe expands more because it is a solid plastic pipe. A RIXc or standard pipe has an aluminium core and therefore expands less.

Vond je dit antwoord nuttig?

There is physical and chemical cross-linking. Tubes are cross-linked to optimise the strength and durability of the tube.

Vond je dit antwoord nuttig?

Chemical cross-linking is achieved by adding peroxide or silane to polyethylene. A physical cross-linking is created by exposing the tube to electron beams. Henco uses physical cross-linking because it is the purest cross-linking.

Vond je dit antwoord nuttig?

National regulation relating to hot water vary between 60- 70°C.

Vond je dit antwoord nuttig?

  1. Lighter weight
  2. Fully modular composition
  3. Prefabricated assembly possible
  4. Re-usable
Vond je dit antwoord nuttig?

No, this is not permitted by law.

Vond je dit antwoord nuttig?

DISINFECTION HENCO PIPES

1. The manufacturer should be consulted before using disinfectant products or applying a thermal cycle where temperatures exceed the specified usage temperature. The following products can be used:

Hadex
Diluted with water at a concentration of 1:13000 (± 4 ppm Bleach) in accordance with the instructions. Treat for a maximum of 5 minutes at 90°C and only perform one treatment per year

Herlisil
Diluted with water at a concentration of 1:1000 (± 500 ppm hydrogen peroxide) in accordance with the instructions. Treat for a maximum of 5 minutes at 90°C and only perform one treatment per year.

Citric acid
Maximum 10% diluted with water. Treat for a maximum of 5 minutes at 90°C and only perform one treatment per year

It should be noted here that these treatments will only have a long-term effect if the source of the contamination is dealt with professionally

2. Disinfection according to DVGW W557
The Henco Multilayer pipes will resist a short period of chemical disinfection in compliance with table 1 of DVGW guideline W557. The maximum allowed concentrations, the maximum allowed temperature, the maximum allowed treatment time and active elements as shown in this table must be strictly observed.

Vond je dit antwoord nuttig?

Specialist advice should be sought from companies such as Promat.

Vond je dit antwoord nuttig?

Henco naked pipes are Euro Class E, in some instances when embedded Henco produce a special sprinkler range that is approved by VdS.

Vond je dit antwoord nuttig?

Yes, for example as ground pipes. In this case, we recommend combining the Henco standard multilayer pipe with the PVDF press fittings. It is best to protect the pipe additionally with, for example, a PVC protective tube. Please note that Henco inspection certificates only apply to indoor installations.

Vond je dit antwoord nuttig?

Yes, at a maximum pressure of 10 bar and ambient temperatures between -10°C and 40°C.

Vond je dit antwoord nuttig?

Only if the soil does not contain any chemicals and the pipe is protected from external damage. Brass fittings should always be protected from corrosion and we also recommend protecting PVDF fittings from external impact with, for example, a PVC pipe.

Vond je dit antwoord nuttig?

The insulation is vapour-proof, but not suitable for long-term outdoor use or applications in moist sandy soil. If the insulation must nevertheless be used in those conditions, it is best to apply a waterproof protective tube (such as a PVC pipe) around the insulation.

Vond je dit antwoord nuttig?

Yes, the pipes may be exposed to sunlight for a short period of time. Polyethylene is not UV-resistant, so Henco tubes should not be permanently exposed. For specific outdoor applications, Henco can produce unique UV-resistant pipes on request.

Vond je dit antwoord nuttig?

The minimum temperature for Henco multilayer pipes and PVDF press fittings is -20°C. For solid plastic pipes, the minimum temperature is 7°C.

Vond je dit antwoord nuttig?

Henco multilayer pipes and PVDF press fittings with gas marking may be used for gas. Please note that gas application is only allowed in countries where a Henco gas inspection and certificate is available.

Vond je dit antwoord nuttig?

Yes, when Henco multilayer pipes are combined with PVDF or brass press fittings with yellow gas marking. For diesel applications, the sealing material should be HNBR (hydrogenated nitrile rubber). HNBR is a type of rubber that is resistant to high temperatures and petroleum-based oils. This is only the case with gas-marked Henco products.

Vond je dit antwoord nuttig?

This is currently being investigated, but we cannot guarantee it yet.

Vond je dit antwoord nuttig?

Only Henco standard multilayer pipes and PVDF fittings qualify for this. The Henco brass products may not come into contact with seawater.

Vond je dit antwoord nuttig?

It can if the paint is water based.

Vond je dit antwoord nuttig?

We recommend draining Henco pipes in good time if there is a risk of freezing. To prevent freezing, pipes can be thoroughly insulated or fitted with a heat tape.

Vond je dit antwoord nuttig?

Yes, in combination with Henco multilayer pipe and PVDF fittings. The brass threaded fittings must not come into contact with softened water.

Vond je dit antwoord nuttig?

Yes, and for fittings this applies to both PVDF and brass fittings. For that application, the correct ratio is 45% glycol and 55% water. The minimum temperature is -10°C.

Vond je dit antwoord nuttig?

The 24P-/25P fitting and a jacketed or pre-insulated pipe.

Vond je dit antwoord nuttig?

The PE foam has a solid PE outer shell with grid structure in red or blue that is also vapour-tight. This structure protects the foam from damage, thus maintaining its insulating effect even during rough construction work.

Vond je dit antwoord nuttig?

Henco tubes up to and including 26 mm diameter can be bent with the appropriate tools from the Henco product range. For pipes with a diameter from 32mm onwards, it is best to use couplings.

Vond je dit antwoord nuttig?

Check which certificates Henco complies with here.

Vond je dit antwoord nuttig?

The correct ratios and temperatures for combining Henco tubes with Hadex -Herlisil and can be found in our technical manual on the Henco website.

Vond je dit antwoord nuttig?

Can Henco tubes be rinsed with hydrogen peroxide/sodium hypochlorite/chlorine dioxide?

When rinsing pipes, it is best to consult the table below. In case of additional questions, please contact your Henco representative.

Table 1: disinfectants for short-term chemical disinfection of Henco ML pipes according to DVGW W577

Title

Commercial packaging

Max. concentration (*)

Maximum duration and temperature

Hydrogen proxide (H2O)

Solution in water 50%

150 mg/l H2O2

Max. 24h

Max. 25°C

Sodium hypochlorite NAOCl

Aqueous solution containing up to 150g/l "free chlorine"

50 mh

Max. 12h

Max. 25°C

Chlorine dioxide ClO2

 

6 mg/l ClO2

Max. 12h

Max. 25°C

 (*) The concentration indicated is that of free chlorine.
Maximum frequency: once a year

Vond je dit antwoord nuttig?

Yes, however mechanical compression using an olive or threaded joints should not be embedded.

Vond je dit antwoord nuttig?

The standard dimension is 153mm, only the 28PV-16031603-1 has a centre distance of 120mm.

Vond je dit antwoord nuttig?